Mounting

Introduction
For the connection of the ET 200AL I/O module via ET-Connection to the ET 200SP, you
require the BaseUnit BU-Send with the BusAdapter BA-Send 1xFC.
Requirement
• The mounting rail is mounted.
• The interface module is mounted.
Required tools
3 to 3.5 mm screwdriver (only for dismantling the BusAdapter)
Mounting BaseUnit BU-Send
To mount the BaseUnit BU-Send, follow these steps:
1. Mount the BaseUnit BU-Send to the right of the CPU/interface module.
2. Swivel the BaseUnit back until you hear the mounting rail release latch into place.
3. Move the BaseUnit to the left until you hear it latch into place on the CPU/interface module.
Figure 5-1
4. Mount the BusAdapter BA-Send 1xFC only after you have connected the bus cable for ET-
Connection (see section Connecting).
Mixed configuration
Equipment Manual, 11/2020, A5E33344611-AD
Mounting BU-Send
5
21