Mounting and Commissioning

8.1
General Information
DANGER
Danger due to high voltages
Non-observance will lead to death or serious injury.
Please read and observe all instructions and warn-
ings contained in this document.
NOTE
For operating heights > 2000 m, a reduction of the test
voltages according to IEC 60255-5 / 60870-2-1 is
necessary.
The installation site must be vibration-proof. The
permitted ambient temperature must be observed
(see the technical data in Chapter 17).
Operating the device outside the permitted operating
temperature range can lead to measuring errors and
device failure.
The terminal of the supply voltage is designed for
conductor cross-sections of 1.5 mm² (AWG 16) to
2.5 mm² (AWG 14) max.
The terminal of the 20-mA inputs (T) and (Q) are
designed for conductor cross-sections of 0.2 mm²
(AWG 24) to 1.5 mm² (AWG 16) max.
The device must not be exposed to condensation
during operation.
The device must be installed in a location where it is
not exposed to direct sunlight and strong temperature
variations.
SICAM AI Unit 7XV5674, Product Information
E50417-B1150-C492-A1, Edition 09.2012
15