Service
F.F 00 00 x2 00
F.F 00 00 x4 00
F.F 00 00 x8 00
F.F 00 00 1x 00
F.F 00 00 2x 00
F.F 00 00 4x 00
F.F 00 00 8x 00
D000030110 d – E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) – User Manual
Backup data checksum error (critical error)
This error message appears when the backup data checksum test fails.
Load profile data will be marked in the status code (bit 2 "corrupted meas-
urement" and bit 0 "critical error" set). The meter may contain incorrect
data and must be exchanged.
The same applies to messages where the bit is set:
F.F .. .. 03/06/07/0A/0B/0E/0F.
Parameter checksum error (critical error)
This error message appears when the parameter checksum test fails.
Load profile data will be marked in the status code (""bit 0 "critical error"
set). The meter may contain incorrect data and must be exchanged.
The same applies to messages where the bit is set:
F.F .. .. 05/06/07/0C/0D/0E/0F.
Load profile 1 checksum error (non-critical error)
Load profile 1 data of the defective memory area will be marked in the
status code (bit 2 "corrupted measurement" set).
The error can be reset via communication. Reset the load profile first
and then the error. If it occurs repeatedly, the meter must be replaced as
soon as possible.
The same applies to messages where the bit is set:
F.F .. .. 09/0A/0B/0C/0D/0E/0F.
Stored values checksum error (critical error)
Data in the defective memory area will be marked in the status code (bit 0
"critical error" set).
The error can be reset via communication. If it occurs repeatedly, the
meter must be replaced as soon as possible.
Event log checksum error (non-critical error)
Data in the defective memory area will be marked in the status code (bit 0
set).
The error can be reset via communication. If it occurs repeatedly, the
meter must be replaced as soon as possible.
Calibration data checksum error (critical error)
Data in the defective memory area will be marked in the status code (bit 0
"critical error" set).
The meter must be replaced as soon as possible.
Load profile 2 checksum error (non-critical error)
Load profile 2 data of the defective memory area will be marked in the
status code.
The error can be reset via communication. Reset the load profile first
and then the error. If it occurs repeatedly, the meter must be replaced as
soon as possible.
The same applies to messages where the bit is set:
F.F .. .. 90/A0/B0/C0/D0/E0/F0.