Installation and De-Installation
4.6

Installation of Terminal Cover Detection

D000030110 d – E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) – User Manual
10. Check the tariff displays and switch the control voltages to the tariff
inputs on and off. The arrow symbols of the tariff display must change.
11. If the meter is connected to a meter readout system via the electrical
interface, a check should be made of correct functioning of the data
transmission.
12. If a GSM modem is connected to the meter, the SMS transmission
function should be checked by sending a test SMS message, e.g. to
your own mobile telephone.
13. Screw on the terminal cover if the meter is operating correctly.
Otherwise first locate and eliminate the error.
14. Seal the terminal cover with two utility seals.
15. Set the current date and time with the relevant formatted command
(see section 5.8 Input of Formatted Commands) or in the set mode
(see section 5.9 Changing Values in Set Mode).
16. Close the front door.
17. Re-seal the front door.
1.
Ensure that control input 1 has been parameterised for this function.
2.
Connect cables 1 and 2 to terminal according to the figure below.
Fig. 4.16
Connection of cables of cover detection unit
3.
Fix terminal cover detection unit to meter. See picture below.
Fig. 4.17
Fixing of cover detection unit to meter
4.
Connect cable 3 as shown above.
55/93
© Landis+Gyr AG