Direction of rotating
field
Total harmonic
distortion
© Landis+Gyr AG
Fig. 1.15
Phase angle case 1
Case 2: The voltage angles are displayed as in case 1. The angles of the
currents are displayed, however, with reference to the associated phase
voltage and can have values between -180° and +180°.
Fig. 1.16
Phase angle case 2
The direction of the rotating field is calculated by the microprocessor based
on the phase angle of the 3 voltages. If the direction of rotation corres-
ponds to that specified by the parameterisation, the phase voltage indica-
tions L1, L2 and L3 are continuously lit. Otherwise they flash every second.
The measuring system produces information about the total harmonic dis-
tortion of the active energy.
For that purpose, the voltages are fed through notch filters, which remove
the fundamental wave.
+A
+THD = +A - (+A
-A
-THD = -A - (-A
Fig. 1.17
Calculation of total harmonic distortion
In addition, the following absolute and relative THD values available:
THD of active energy (relative to the nominal active energy)
THD of phase voltages (absolute)
THD of voltage (relative to the nominal voltage)
THD of phase currents (absolute)
THD of phase current (relative to the nominal current)
D000030110 d – E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) – User Manual
)
A
fundamental
)
A
fundamental
Description of Unit
+THD
A
-THD
A