Maintenance Instructions - L.B. White Commander Owner's Manual And Instructions

Ductable make-up air heaters
Table of Contents

Advertisement

Available languages

Available languages

16
Commander Ductable Make-Up Air Heater
WARNING
Do not use a pressure washer, water, or liquid
cleaning solution on any gas controls. Use of a
pressure washer, water, or liquid cleaning solution on
the control components can cause severe personal
injury or property damage due to water and/or liquids:
■ In electrical components, and wires causing
electrical shock or equipment failure.
■ On gas control valves causing corrosion which can
result in gas leaks and fire or explosion from the
leak.
Clean all components of the heater with pressurized
air, a dry brush, or a dry cloth.

Maintenance Instructions

BEFORE EACH USE:
• Check the area surrounding the heater to ensure it is
clear and free of combustible materials, gasoline, and
other flammable vapors and liquids.
• Have your gas supplier check all gas connections for
leaks or restrictions in gas lines.
• Inspect the regulator vent to make sure the regulator
vent is not blocked. Debris, insects, insect nests,
snow, or ice on a regulator can block vents and cause
excess pressure at the heater.
• Check all wiring associated terminals and electrical
components within the heater for corrosion, frayed
or cut insulation, tight connections, etc. Repair or
replace as necessary.
• Check the hose assembly after heater installation,
relocation and when the heater is in use. If it is
evident there is excessive abrasion or wear, or if the
hose is cut, it must be replaced prior to the heater
being put back into operation.
• The heater's fan wheel should be checked
periodically for damage and cleanliness.
Owner's Manual •
Commander Ductable Make-Up Air Heater
• Review all heater markings (i.e. wiring diagram, warnings,
start-up, shut-down, troubleshooting, etc.) at the time of
maintenance for legibility. Make sure none are cut, torn,
or otherwise damaged. Any damaged markings must be
replaced immediately by contacting the L.B. White Co.,
LLC. Data plate, startup and shut-down instructions and
warnings are available at no cost.
MONTHLY:
• Inspect caster wheels and fan wheel for damages.
• Clean/remove any dust build up on the motor.
• Check motor mounting bolts for tightness.
ANNUALLY:
• Clean and check the igniter for cracks. Replace if
necessary.
• Grease the swivel caster wheels ball bearings with a
Lithium based grease.
• Regulators can wear out and function improperly. Have
your gas supplier check the date codes on all regulators
installed and check delivery pressures to the heater to
make sure that the regulator is reliable.
• Test the resetable high limit switch to ensure proper
operation. See page 19.