Goodrive800 Pro Series Regenerative Rectifier Hardware Manual
To fix the bottom support crossbeams and install the unit tray:
(1) Use ten M8 cage nuts to fix the five bottom support crossbeams to the base of the nine-fold profile
cabinet frame. (For the support crossbeams, T≥2.0mm, firmly installed)
(2) Fix the mounting bracket to the nine-fold profile cabinet frame base with twenty M5 self-tapping screws.
See Figure 3-9.
(3) Install the unit tray on the support crossbeams with ten M8 screws. See Figure 3-10.
(4) If you use another type of cabinet but not nine-fold profile cabinet, the fixing holes for the mounting
bracket need to be drilled and assembled on site.
Figure 3-10 Installing the support crossbeams
Five crossbeams must be installed at the
cabinet bottom to support the unit.
(Recommended material thickness≥2.0mm)
3.3.6.2 Layout and mounting for L+A8
Figure 3-12 shows the 600mm-wide cabinet layout for L+A8.
202308 (V1.1)
Figure 3-12 Layout of 600mm-wide cabinet for L+A8
Figure 3-11 Installing the unit tray
Unit bottom installation tray
Nine-fold profile cabinet
Mechanical installation