Function C: Range Settings; Span (Range) (Function C) - Toshiba LF620 B Series Instruction Manual

Electromagnetic flowmeter converter
Table of Contents

Advertisement

Switch operation
STEP4(=END)
Note : The selectable characters are displayed cyclically as shown below:
Symbol 1
Numeric
characters
Symbol 1
Alphabetical
characters
(uppercase)
Alphabetical
characters
(lowercase)
Special
character

Function C: Range Settings

8.2.9 Span (Range) (Function C)

You can set the following constants in this setting item:
(1) Range type
(2) Unit of span (can be changed in Range 1)
(3) Span
(4) Hysteresis
● Range type
Multiple ranges can be used by selecting the range type. You can select a single range,
multiple ranges, or forward/reverse multiple ranges.
Select one from five types shown below:
Display example
CS UNIT
XXX/ZZZ
SET OK?
O K
ESC
! " # $ % & ' ( ) * + , - . /
0~9
: ; < = > ? ・
A~Z
a~z
" "(Space)
Selection items (display)
SINGLE
4F-0R
2F-2R
EXT 2F-0R
EXT 2F-2R
- 66 -
Description
Pushing
when the cursor is positioned
on the 7th character shows a message to
confirm whether the setting is OK or not.
O K
If OK, push
N O
setting, push
Pushing
cancels the setting operation
ESC
and exits the setting screen.
N O
Description
Single range
Unidirectional flow,
automatic selection of multiple ranges
Bidirectional flows,
automatic selection of multiple ranges
Unidirectional flow,
multiple ranges selected by external signal
Bidirectional flows,
multiple ranges selected by external signal
6 F 8 A 0 9 9 7
. If you want to redo the
.