Electromagnetic flowmeter

Advertisement

Quick Links

Field Intelligent Device
ELECTROMAGNETIC FLOWMETER
Introduction
The electromagnetic flowmeter uses Faraday's Law of
electromagnetic induction to measure the process flow.
The device consists of two units: a detector, through
which the fluid to be measured flows and in which
low-level signals proportional to flow rates are
obtained; and a converter, which supplies excitation
current to the detector, and amplifies the signals from
the detector and then processes and converts the signals
into the 4–20 mAdc current signal or communication
signal. Combined with a multi-functional converter
LF622 (separate type) equipped with its patented
Noise-Sentry original noise- suppression circuit and
advanced algorithms. The GF642 has a very high
tolerance to noise, giving the unit a very stable output
even for slurry fluid measurement. IR (Infrared)
switches enable parameter setting of the converter
without removing the cover. Flow direction can be set in
either way.
The AF900 hand-held terminal (HART
can be used to communicate with the flowmeter from a
remote place. PROFIBUS-PA
is available as an option.
*1:
HART protocol (Highway Addressable Remote Transducer)
is a communication protocol for industrial sensors
recommended
by
the
Foundation).
*2: PROFIBUS is the communications protocol for factory and
process automation that the PROFIBUS Organization
recommends. Instead of analog control with a conventional
analog signal (4-20 mA), it is fieldbus which digitizes all
signals. Flowmeters support PROFIBUS-PA.
*3:Modbus is the communication protocol that Modicon Inc.
developed. Physical layer is RS485.
C o n v e r t e r ( L F 6 2 2 )
P o w e r c a b l e
S i g n a l a n d E x c i t a t i o n c a b l e
Figure1. Configuration
Certification
number
Z01207
*1
communicator)
*2
*3
or Modbus
interface
HCF
(HART
Communication
D e t e c t o r ( G F 6 4 2 )
20" to 80"(500mm to 2000mm)
Figure2. GF642 Flowmeter
General Specifications
Measurement range: (measuring range by flow
Meter size
Measuring range
Accuracy: (Accuracy when combined with the
converter LF622)
Flow rate
1.0 ~ 3.28 ft.s
(0.3 ~ 1.0m/s)
0 ~ 100%FS
±0.8% FS
Note: The accuracy above is measured under
standard operating conditions using the
weighing method at Toshiba admitted
flow calibration facility.
Fluid conductivity:
5µS/cm minimum
Fluid temperature:
14 to 140 °F (-10 to +60℃)
: 20" to 36" (500mm to 900mm)
14 to 104 °F (-10 to +40℃)
: More than 40" (more than 1000mm)
GF642/LF622
(Separate type)
rate conversion)
From 20" to 80"
(500mm to 2000mm )
0-1.0ft/s to 0-32.8ft/s
(0-0.3m/s to 0-10m/s)
Flow speed of full scale
3.28ft/m ~ 32.8ft/s
(1.0 ~ 10m/s)
±0.5 %FS
EJL-146C

Advertisement

loading

Summary of Contents for Toshiba GF642

  • Page 1 Combined with a multi-functional converter LF622 (separate type) equipped with its patented Noise-Sentry original noise- suppression circuit and advanced algorithms. The GF642 has a very high tolerance to noise, giving the unit a very stable output even for slurry fluid measurement. IR (Infrared) switches enable parameter setting of the converter without removing the cover.
  • Page 2 EJL-146C Ambient temperature: Specifications of LF622(Separate type) 14 to 140 °F (-10 to +60℃) Converter Input signals: Storage temperature: Analog signal: 5 to 149 °F (-15 to +65℃) The voltage signal from detector. Proportional to process flow rate Digital input DI: Storage humidity: Signal type: 20 to 30Vdc voltage signal...
  • Page 3 EJL-146C Pulse output (available only for DO1, DO2): LCD display: Pulse rate: Full dot-matrix 128×128 display Max 10kHz (10,000pps) (DO1) (back-light provided) Max 100Hz ( 100pps) (DO2) Parameter setting: (Over 1kpps, auto-setting) Parameters can be set as follows: Pulse width: IR Switches: 0.3 to 500ms (but less than half of the period Tree...
  • Page 4 EJL-146C Vibration resistance: No resonance to the following levels of vibration: ・10 to 150Hz with acceleration of 9.8m/s ・Vibration of 30Hz with 29.4m/s in 4h in each direction will not cause any defect to unit. Note: Avoid using the flowmeter in an environment with constant vibration.
  • Page 5: Installation

    1715 1200 1600 1600 1892 1200 1600 1600 1935 1700 1800 1800 1078 2101 1700 1800 1800 1078 2136 2200 2000 2000 1180 2313 2200 2000 2000 1180 2343 3000 Figure 3: GF642 Meter 20” to 80” (500mm to 2000mm)
  • Page 6: External Connection

    EJL-146C External Connection Instrument panel : Ordered separately Grounding with 100Ω or less Ⅳ wire 5.5mm or more ground resistance Power switch Grounding with 100Ω or less (External double-pole power switch) ground resistance Power supply Thick walled steel conduit Current output (4~20mAdc) Signal cable or PROFIBUS (2-wire shielded hard-rubber sheathed cable)
  • Page 7 EJL-146C Wiring Precautions (8) When wiring is completed, male sure to install the terminal block protection cover. (1) Connect the grounding wire (IV wire 5.5mm² or (9) Do not carry out withstand voltage test for the more) to a good earth ground (100Ω or less ground resistance).
  • Page 8: Piping Precautions

    EJL-146C subject to change or review without prior notice. Piping Precautions (1) Design piping so that the flowmeter detector pipe is always filled with the fluid being measured, whether the fluid is flowing or not. (2) The detector has no adjustable piping mechanism.
  • Page 9: Type Specification Code

    EJL-146C Type Specification Code Table4. Type specification code of detector Model number Specification code Contents 2 3 4 5 6 7 8 G F 6 4 2 Electromagnetic flowmeter detector ● ● Meter size 500mm ● ● 600mm ● ● 700mm ●...
  • Page 10 EJL-146C Table5. Type specification code of converter Model number Specification code Contents 9 10 11 12 LF622 Electromagnetic flowmeter converter (Separate type) Purpose Standard ● Shape Standard type with case ● Converter mounting fitting None ○ Panel, Accessory for wall mounting ●...
  • Page 11 ISO9001 and ISO14001 are certified. Specifications are subject to change without notice. Printed in Japan 2017-07 © Toshiba Infrastructure Systems & Solutions Misuse of this product can result in damages to property or human injury. Corporation 2017 Read related manuals carefully before using this product.