Table 2-7 Cables to be prepared by the customer in the 4G LTE network scenario
No.
Cable
1
Three-phase AC
power cable
3
Peripheral RS485
communications
cable
4
Cabinet PE cable
5
Network cable
from the PoE
module or PoE
SPD to the CPE
6
Single-phase AC
power cable
Issue 05 (2023-09-26)
Recommended Model or
Specifications
● Four-core (L1, L2, L3, and FE)
outdoor armored copper cable and
OT-M4 terminals (FE)
● When the rated AC voltage on the LV
side of the transformer station is less
than or equal to 500 V, the operating
voltage between the three-phase AC
power cable and the ground should
be greater than or equal to 600 V.
● When the rated AC voltage on the LV
side of the transformer station is
greater than 500 V and less than or
equal to 800 V, the operating voltage
between the three-phase AC power
cable and the ground should be
greater than or equal to 1000 V.
Computer cable (DJYP2VP2-22 2x2x1)
or armored shielded twisted pair that
can be used outdoors, as well as OT-M4
terminals
Outdoor copper cable and OT-M6
terminals
20 m (65.62 ft) long network cable
delivered with the Huawei CPE. If the
cable is not long enough, prepare a Cat
5e outdoor shielded network cable with
an outer diameter of less than 9 mm
(0.35 in.) and internal resistance of less
than or equal to 1.5 ohms/10 m (1.5
ohms/32.81 ft), as well as shielded RJ45
connectors.
● Standard connection: two-core
outdoor armored copper cable
● Connection through a pipe: single-
core outdoor copper cable
● Operating voltage to the ground ≥
300 V
Copyright © Huawei Technologies Co., Ltd.
2 Overview
Cross-sectional Area
Range of the Cable
(Recommended Value)
2
● 4–10 mm
(10 mm
● 8 AWG
2
● 0.5–1 mm
(1 mm
● 20–18 AWG (18 AWG)
2
● 6–16 mm
(16 mm
● 10–6 AWG (6 AWG)
-
2
2
● 4–6 mm
(4 mm
● 12–10 AWG (12 AWG)
2
)
2
)
2
)
)
35