Table with error codes
Error code
Meaning
(DW#16#...)
00000000
No error.
10010000
The assigned number of the digital input at the Channel
input parameter is outside the permitted range
(depending on addressed module and channel
configuration).
10020000
The TIO_DI instruction is not called in an isochronous
OB. The instruction can only be used without errors in an
isochronous OB.
10030000
An error occurred when reading the HWID input
parameter.
x0040000
The data in TIO_SYNC_Data is invalid/incorrect.
1005xxxx
An error has occurred during execution of the RD_SINFO
system function. The low word xxxx displays the error
information of the RET_VAL return value from
RD_SINFO.
10060000
Unable to find TM Timer DIDQ.
Possible cause:
The module configured using the hardware identifier is
not a TM Timer DIDQ.
10070000
An internal error occurred during the address calculation. Check the value at the HWID input parameter.
00080000
TIO module is not synchronized using the TIO_SYNC
instruction.
10090000
The read cycle time of the isochronous OB is outside the
permitted range of 0 < T
invalid.
The instruction can only be used without errors in an
isochronous OB.
100A0000
The assigned time at the TO input parameter is outside
the permitted range of 0 < T
100Bxxxx
An error has occurred during execution of the RD_ADDR
system function. The low word xxxx displays the error
information of the RET_VAL return value from
RD_ADDR.
High-precision input/output with Time-based IO
Function Manual, 08/2014, A5E33454822-AB
<= 16 ms and is therefore
APP
<= 4 ms.
o
Remedy
Correct the value at the Channel input
parameter.
Make sure that TIO_DI is called in a
"Synchronous Cycle" OB.
Check the value at the HWID input parameter.
Specify the hardware identifier of the TIO module
from its module properties in HWCN. An internal
system constant of data type Hw_SubModule is
available for the symbolic addressing.
Check the TIO_SYNC instruction and the
interconnection of its TIO_SYNC_Data output.
Read the description of the RD_SINFO in the
TIA Portal information system.
Make sure that TIO_DI is called in a
"Synchronous Cycle" OB.
Make sure that the configured module is a
TM Timer DIDQ.
Check the value at the HWID input
parameter. Specify the hardware identifier of
the TIO module from its module properties in
HWCN.
Specify the hardware identifier of the TIO module
from its module properties in HWCN. An internal
system constant of data type Hw_SubModule is
available for the symbolic addressing.
Check the instruction TIO_SYNC.
Correct the cycle time.
Make sure that TIO_DI is called in a
"Synchronous Cycle" OB.
Correct the value at the TO input parameter.
Read the description of the RD_ADDR in the
TIA Portal information system.
Programming
4.3 Time-based IO
45