Error code
Meaning
(DW#16#...)
10070000
An internal error occurred during the address calculation.
00080000
TIO module is not synchronized using the TIO_SYNC
instruction.
10090000
The read cycle time of the isochronous OB is outside the
permitted range of 0 < T
invalid.
The instruction can only be used without errors in an
isochronous OB.
100A0000
The assigned time at the TO input parameter is outside
the permitted range of 0 < T
100Bxxxx
An error has occurred during execution of the RD_ADDR
system function. The low word xxxx displays the error
information of the RET_VAL return value from RD_ADDR.
000C0000
The time stamp at the TimeStamp input parameter is
invalid.
000D0000
The value status PortQualifier of the IO-Link indicates that
the process data is invalid.
100E0000
The configured port mode of the IO-Link is incorrect.
100F0000
The read cycle time of the "Synchronous Cycle" OB is too
long. T
APP
x0FF0000
General internal error.
High-precision input/output with Time-based IO
Function Manual, 08/2014, A5E33454822-AB
<= 16 ms and is therefore
APP
<= 4 ms.
o
> 16 ms.
Remedy
Check the value at the HWID input parameter.
Specify the hardware identifier of the TIO
module from its module properties in HWCN.
An internal system constant of data type
Hw_SubModule is available for the symbolic
addressing.
Check the instruction TIO_SYNC.
Correct the cycle time.
Make sure that TIO_IOLink_OUT is called in
a "Synchronous Cycle" OB.
Correct the value at the TO input parameter.
Read the description of the RD_ADDR in the
TIA Portal information system.
Check the TimeStamp input parameter.
Check the connected sensor and its
configuration.
Check the configuration of the connected
sensor with S7-PCT.
Configure a smaller multiple of the send clock
as the cycle time.
Programming
4.3 Time-based IO
51