Configuring and parameter assignment
3.3 Configure IO-Link and activate Time-based IO
Procedure
1. Right-click the IO-Link Master in the TIA Portal and select "Start Device Tool".
The Port Configuration Tool (S7-PCT) opens.
2. Select the connected IO-Link Device (sensors/actuators with time stamp function) from
the device catalog for the ports of the IO-Link Master in S7-PCT.
Use drag-and-drop to insert the IO-Link Device to the matching Port of the IO-Link
Master.
3. Adapt the settings of the ports to match their respective task in the application.
Possible port settings:
– IO-Link Time based IN: The input signals of the sensor are given a time stamp.
– IO-Link Time based OUT: The signal is output at the specified time.
4. Save the settings.
5. Download the Port configuration to the IO-Link Master.
6. Close S7-PCT.
Result
The IO-Link Master is configured with the connected sensor and actuator information.
28
High-precision input/output with Time-based IO
Function Manual, 08/2014, A5E33454822-AB