Error code
Meaning
(DW#16#...)
10080000
Isochronous mode missing. Time-based IO cannot be
used.
Possible cause:
Internal error during address calculation
10090000
TIO module HWID_1: Error during reading of HWID_1.
100A0000
TIO module HWID_2: Error during reading of HWID_2.
100B0000
TIO module HWID_3: Error during reading of HWID_3.
100C0000
TIO module HWID_4: Error during reading of HWID_4.
100D0000
TIO module HWID_5: Error during reading of HWID_5.
100E0000
TIO module HWID_6: Error during reading of HWID_6.
100F0000
TIO module HWID_7: Error during reading of HWID_7.
10100000
TIO module HWID_8: Error during reading of HWID_8.
10110000
The configured process image partition at input
parameter PIP_PART is not within the valid range of 1 to
31.
x0FF0000
General internal error.
High-precision input/output with Time-based IO
Function Manual, 08/2014, A5E33454822-AB
Remedy
Check the values of input parameters HWID_1
to HWID_8. Specify the hardware identifier of
the TIO module from its module properties in
HWCN.
Check the value of the respective input
parameter. Specify the hardware identifier of the
TIO module in each case from its module
properties in HWCN. An internal system
constant of data type Hw_SubModule is
available for the symbolic addressing.
Correct the value at the PIP_PART input
parameter.
Programming
4.3 Time-based IO
37