General Gas Supply Layout (Example) - Riello DR 32 SE FGR Installation, Use And Maintenance Instructions

Industrial gas burner
Table of Contents

Advertisement

Available languages

Available languages

4.8.2

General gas supply layout (example)

20160046
Key (Fig. 16)
AD2
Primary air damper
AD3
Secondary air damper
BP
Pilot burner
AVJ
Vibration damping joint
GF
Gas filter
GV
Gas butterfly valve
HPG
High gas pressure regulator
LPG
Low gas pressure regulator
MM
Pressure gauge
PA
Minimum air pressure switch
VPS
Gas pressure sensor
PGm
Minimum gas pressure switch
PGM
Maximum gas pressure switch
SM1
Fuel servomotor
SM2
Primary air servomotor
SM3
Secondary air servomotor
PCV
Pilot gas pressure regulator
SRV Vent
Solenoid (Safety)
SSV
Manual reset stop valve
VA
Pilot air pressure regulation valve
VC
Continuous purging solenoid
VE
Fan
VR
Gas pressure regulator solenoid valve
VP
Gas safety solenoid
PGmP
Minimum gas pressure switch for pilot
RGP
Gas train for pilot burner
Installation
19
GB
PART THAT IS THE RESPONSIBILITY
OF THE INSTALLER/USER
Fig. 16