Electrical wiring of the flame detector
It is important for signal transmission to be almost totally free
of any disturbances or loss:
• Always separate the detector cables from the other cables:
– Line capacitance reduces the magnitude of the flame signal.
– Use a separate cable.
• Respect the allowed cable lengths.
Technical data
LMV52... base
Mains voltage
control box
Mains frequency
Power absorption
Safety class
Load on 'input'
F1 unit fuse (internal)
terminals
Primary perm. mains fuse (external)
Undervoltage
• Safety switch-off from operating position
to mains voltage
• Restart when mains voltage picks up
Oil pump / magnetic clutch (nominal voltage)
• Nominal current
• Power factor
Air pressure switch test valve (nominal voltage)
• Nominal current
• Power factor
Load on 'output'
Total load on the contacts:
terminals
• Mains voltage
• Total unit input current
(safety circuit)
load on contacts due to:
- Fan motor contactor
- Ignition transformer
- Valve
- Oil pump / magnetic clutch
Single contact loading:
Fan motor contactor (nominal voltage)
• Nominal current
• Power factor
Alarm output (nominal voltage)
• Nominal current
• Power factor
Ignition transformer (nominal voltage)
• Nominal current
• Power factor
Fuel gas valve (nominal voltage)
• Nominal current
• Power factor
Fuel oil valve (nominal voltage)
• Nominal current
• Power factor
Cable length
Main line
Environmental
Operation
conditions
Climatic conditions
Mechanical conditions
Temperature range
Humidity
20188797
Technical description of the burner
14
GB
AC 230V -15% / +10%
50 / 60 Hz ±6%
< 30W (normal)
I, with components in compliance with II and III, according to
DIN EN 60730-1
6.3 AT
Max. 16 AT
< AC 186V
> AC 188V
2A
cos  > 0.4
0.5A
cos  > 0.4
AC 230V -15 % / +10%
Max. 5 A
1A
cos  > 0.4
1A
cos  > 0.4
2A
cos  > 0.2
2A
cos  > 0.4
1A
cos  > 0.4
Max. 100 m (100 pF / m)
DIN EN 60721-3-3
Class 3K3
Class 3M3
-20...+60°C
< 95% RH
Tab. F