Module Status Leds - Rockwell Automation ICSTT-RM280N-EN-P Manual

Trusted tmr 24 vdc digital output module - 40 channel
Table of Contents

Advertisement

4. Operation

4.2. Module Status LEDs

There are six Module status indicators on the Module Front Panel: three Healthy, one
Active, one Standby, and one Educated. The Healthy indicators are controlled directly by
each Module slice. The Active, Standby, and Educated indicators are controlled by the FPU.
The FPU receives data from each of the Module slices. It performs a 2oo3 vote on each data
bit from the slices and sets the indicators accordingly.
The Module status indicator modes and their meanings are described as follows:
INDICATOR
STATE
Healthy
Off
Amber
Green
Red – flashing
Red (momentary)
Red
Active
Off
Green
Red – flashing
Red – flashing
Standby
Off
Green
Red – flashing
26
Trusted TMR 24Vdc Digital Output Module – 40 Channel
DESCRIPTION
No power applied to the Module.
Slice is in the start-up state (momentary after installation
or power-up).
Slice is healthy.
Fault present on the associated slice but the slice is still
operational.
On installation – power applied to the associated slice.
The associated slice is in the fatal state. A critical fault has
been detected and the slice disabled.
Module is not in the Active state.
Module is in the Active (or Maintain) state.
Module is in the shutdown state if the Standby LED is off.
Module is in the fatal state if the Standby LED is also
flashing.
Module is not in the Standby state.
Module is in the Standby state.
Module is in the fatal state. The Active LED will also be
flashing red.
Issue 14
Rockwell Automation Publication ICSTT-RM280N-EN-P

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pd-t8451

Table of Contents