Trusted TMR 24Vdc Digital Output Module – 40 Channel
The IEC 61131 TOOLSET conversion tables may be used to convert the value to engineering
units, in this case current. The full-scale range for this number format is decimal ±32,
corresponding to physical range –32000 to +32000.
3.2.5.

Rack 5: LINE_FLT

The line fault input state is reported as true (logic '1') for a line fault condition (open circuit,
short circuit, and no field supply voltage). The logic state is the majority voted value.
3.2.6.

Rack 6: DISCREP

Each of the words reports the discrepancy status of 16 output channels. The corresponding
bit within the word is set to '1' when a discrepancy condition is detected on that output
channel's output state (Rack 2).
Rockwell Automation Publication ICSTT-RM280N-EN-P
Channel
Description
1
Field output channel 1 line fault
2
Field output channel 2 line fault
40
Field output channel 40 line fault
Table 10 Rack 5: LINE_FLT Descriptions
Channel
Description
1
Discrepancy status outputs 1 to 16
(output 1 is LSB)
2
Discrepancy status outputs 17 to 32
(output 17 is LSB)
3
Discrepancy status outputs 33 to 40
(output 33 is LSB)
Table 11 Rack 6: DISCREP bit Descriptions