2. Installation
2.5. Trusted Module Polarisation/Keying
All Trusted Modules have been Keyed to help prevent insertion into the wrong position
within a Chassis. The polarisation comprises two parts; the Module, and the associated field
cable.
Each Module type has been keyed during manufacture. The organisation responsible for the
integration of the Trusted System must key the cable by removing the keying pieces from
the cable so that they correspond with the bungs fitted to the associated Module prior to
fitting.
Polarising/Keying
Pins.
(Remove using
side cutters where
identified below)
For Cables with Companion slot installations both keying strips must be polarised.
For this Module (T8451) remove keying pins 1, 5 and 6.
14
Trusted TMR 24Vdc Digital Output Module – 40 Channel
1
Trusted Cable
hood
12
Figure 5 Module Polarisation
Issue 14
Cable Exit
Smart
Swap
Connector
if Fitted
Release button
Rockwell Automation Publication ICSTT-RM280N-EN-P