13.2 Maintenance

Maintenance intervals In compliance with EN 60079-17, Ex certified products either require repeated testing
Manual operation During maintenance, the mechanical parts of the handwheel activation, in particular
Lubrication •
Notes relating to mainten-
ance
at an interval of 3 years or continuous monitoring by trained personnel.
motor coupling, must be checked. Replace the parts in case of visible wear.
In the factory, the gear housing is filled with grease.
Additional lubrication of the gear housing is not required during operation.
Grease change is performed during maintenance
Generally after 4 to 6 years for modulating duty.
Generally after 6 to 8 years if operated frequently (open-close duty).
Generally after 10 to 12 years if operated infrequently (open-close duty).
We recommend replacing the seals when changing the grease.
Perform visual inspection of actuator and mounted accessories. Ensure that no
outside damage, changes or leakage of grease and oil are visible.
Check actuator for unusual running or grinding noise or vibration which might be
an indication of bearing or gear damage.
Electrical connection cables must be placed properly and in perfect condition.
Thoroughly touch up any possible damage to painting to prevent corrosion. Ori-
ginal paint in small quantities can be supplied by AUMA.
Check whether Ex connections are fastened correctly.
Take care of possible discolouration of the terminals and wires. This would indic-
ate an increased temperature.
For Ex housings, pay special attention to a possible collection of water. This may
originate from "breathing" due to severe temperature variations (e.g. change of
night and day), from damaged seals etc. Remove any water immediately.
The process temperature range must be within the range of the specified ambient
temperature.
Check the flame path gaps of flameproof enclosures for dirt and corrosion.
Since the dimensions of all flameproof joints are strictly defined and inspected, no
mechanical work (such as grinding) shall be performed on them. The joint sur-
faces have to be cleaned chemically (e.g. with Esso-Varsol).
Consult manufacturer for indications regarding flameproof joints.
Repair interventions on flameproof joints is not permitted.
Prior to fitting, preserve joint surfaces with an acid-free corrosion protection agent
(e.g. Esso Rust-BAN 397).
Thoroughly handle all housing covers and check sealing elements.
All cable and motor protection components have to be checked.
If defects impairing the safety are detected during maintenance, repair measures
have to be initiated without delay.
Any kind of surface coating for the joint surfaces is not permitted.
When replacing parts, sealing elements, etc. only original spare parts shall be
used.
Cables and wire entries, blanking plug, cable glands, plugs etc. have to be
checked for correct tightness and sealing. Consider torques according to manufac-
turer's details. If required, replace the components. Only use components with ap-
propriate Ex approval.
Servicing and maintenance
45