WARNING
How to proceed 1. Remove cable sheathing and insert the wires into the cable glands.
6.2.3 Close motor connection compartment
How to proceed 1. Clean sealing faces of cover [1] and housing.
Type
Speed
SAEx 40.1
4 – 45
In case of a fault: Hazardous voltage while protective earth conductor is
NOT connected!
Risk of electric shock
à Connect all protective earth conductors.
à Connect PE connection to external protective earth conductor of connection cable.
à Power the device only once the protective earth conductor has been connected.
2. Fasten cable glands with the specified torque to ensure required enclosure protec-
tion. For shielded cables: Link the cable shield end via the cable gland to the
housing (earthing).
3. Strip wires.
4. For flexible cables: Use wire end sleeves according to DIN 46228.
5. Connect cables according to order-related wiring diagram.
6. Firmly tighten protective earth to PE connection (symbol
WARNING! In case of fault: Hazardous voltage while protective earth con-
ductor is NOT connected!
Figure 26: Close motor connection compartment
[4]
[1]
Cover
[3]
O-ring
2. Check whether O-ring [3] is in good condition, replace if damaged.
3. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and insert
it correctly.
4. Fit cover [1] and fasten screws [2] evenly crosswise.
Terminal cross sections
2
2.5 – 35 mm
[3]
[2]
[1]
[2]
Screws for cover
[4]
Cable gland
Electrical connection
Tightening torques
3.5 Nm
).
25