Completing The Test; Phase Preference Logic Ppl2Phiz - ABB Relion 670 Series Commissioning Manual

Transformer protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 504 165-UEN E
preference logic shall be set to values according to the real set values to be used. The test is
made by means of injection of voltage and current where the amplitude of both current and
voltage and the phase angle between the voltage and current can be controlled.
During the test the following binary signals (outputs) shall be monitored:
Trip signal from distance protection
Start signal from phase preference logic
1.
Connect the test set for injection of voltage and current.
2.
Inject voltages and currents corresponding to a phase-to-phase to earth fault within zone
1 of the distance protection function. In the test one of the current inputs (one of the
faulted phases) is disconnected. The remaining current is the fault current out on the
protected line. All combinations of two phase-to-earth faults with one phase current are
tested. The result shall be according to table 36. It should be checked that the fault will
give phase-to-phase voltage, phase-to-earth voltage, zero-sequence voltage and phase
current so that the conditions set for the logic are fulfilled.
Table 36: Operation at different combinations of faults and operation mode
OperMode
No Filter
No Pref
1231c
1321c
123a
132a
213a
231a
312a
321a
11.4.14.1

Completing the test

continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
11.4.15

Phase preference logic PPL2PHIZ

Prepare the IED for verification of settings outlined in Section
settings".
The Phase preference logic function PPL2PHIZ is tested with a three-phase testing equipment
for distance protections. PPL2PHIZ is tested in co-operation with the High speed distance
protection ZMFPDIS . The distance protection and the phase preference logic shall be set to
values according to the real set values to be used. The test is made by means of injection of
voltage and current where the amplitude of both current and voltage and the phase angle
between the voltage and current can be controlled.
During the test the following binary signals (outputs) shall be monitored:
Transformer protection RET670
Commissioning manual
Fault type/Faulted phase current to the IED
L1L2N/IL1
L1L2N/IL2
L2L3N/IL2
Trip
Trip
Trip
Trip
Trip
No Trip
No Trip
Trip
Trip
No Trip
Trip
No Trip
No Trip
Trip
No Trip
Trip
Trip
No Trip
No Trip
Trip
© Copyright 2017 ABB. All rights reserved
L2L3N/IL3
L3L3N/IL1
Trip
Trip
Trip
Trip
Trip
Trip
Trip
No Trip
No Trip
No Trip
Trip
Trip
Trip
No Trip
Trip
No Trip
Trip
Trip
Trip
No Trip
Trip
Trip
No Trip
No Trip
No Trip
Trip
No Trip
No Trip
Trip
No Trip
Testing functionality by secondary injection
L3L1N/IL3
Trip
Trip
Trip
No Trip
No Trip
No Trip
No Trip
Trip
Trip
Trip
GUID-8BD66BC8-AAC3-41C4-B819-B159361688D2 v4
TESTMODE setting to Off .
GUID-E1547542-1407-4488-AD99-2A7D063885A4 v1
"Preparing the IED to verify
Section 11
157