ABB Relion 670 Series Commissioning Manual page 223

Transformer protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 504 165-UEN E
1.
Connect the analog signals to the voltage inputs, in pair of two for U1 and U2. (Inputs
U3PBB1, U3PBB2, U3PLN1, U3PLN2)
2.
Activate the binary signals according to the used alternative. Verify the measuring
voltage on the synchronizing check function SESRSYN. Normally it can be good to verify
synchronizing check with the same voltages and phase angles on both voltages. The
voltages should be verified to be available when selected and not available when another
input is activated so connect only one voltage transformer reference at each time.
3.
Record the voltage selection tests in a matrix table showing read values and AUTOSYOK/
MANSYOK signals to document the test performed.
Testing the voltage selection for 1 1/2 CB arrangements
At test of the SESRSYN function for a 1½ CB diameter the following alternative voltage inputs
can be used for the three SESRSYN (SESRSYN 1, SESRSYN 2, SESRSYN 3) functions. These three
SESRSYN functions can either be in one, two or three different IEDs. Table
scenario when SESRSYN 1, SESRSYN 2 and SESRSYN 3 all are in the same IED. If SESRSYN 3 is in
another IED, WA1 will be considered as WA2 and LINE2 as LINE1. The voltage is selected by
activation of different inputs in the voltage selection logic as shown in table
Table 39: Voltage selection logic
SESRSYN
SESRSYN 1
(Operates on
WA1_QA1)
SESRSYN 2
(Operates on
TIE_QA1)
SESRSYN 3
(Operates on
WA2_QA1)
Transformer protection RET670
Commissioning manual
CBConfig
Section to
Activated
setting
be
B1QCLD
synchroniz
input on
ed
IED from
1 ½ bus CB
WA1 –
LINE1
WA1 –
LINE2
WA1 –
WA2
Tie CB
LINE1 –
LINE2
WA1 –
LINE2
WA2 –
LINE1
WA1 –
WA2
1 ½ bus
WA2 –
alt. CB
LINE2
(mirrored)
WA2 –
LINE1
WA2 –
WA1
© Copyright 2017 ABB. All rights reserved
Testing functionality by secondary injection
Activated
Activated
B2QCLD
LN1QCLD
input on
input on
IED from
IED from
LINE1_QB
9
TIE_QA1
TIE_QA1
WA2_QA1
LINE1_QB
9
WA1_QA1
WA2_QA1
LINE1_QB
9
WA1_QA1
WA2_QA1
TIE_QA1
LINE1_QB
9
TIE_QA1
WA1_QA1
Section 11
GUID-12E7DA63-FE04-4C83-9BA6-34818C510DB8 v4
39
describes the
39
and figure 57.
Activated
Indication
LN2QCLD
from
input on
SESRSYN
IED from
on IED
B1SEL,
LN1SEL
LINE2_QB
B1SEL,
9
LN2SEL
B1SEL,
B2SEL
LINE2_QB
LN1SEL,
9
LN2SEL
LINE2_QB
B1SEL,
9
LN2SEL
B2SEL,
LN1SEL
B1SEL,
B2SEL
LINE2_QB
B2SEL,
9
LN2SEL
B2SEL,
LN1SEL
B1SEL,
B2SEL
217