1MRK 504 165-UEN E
Self-supervision status: Main menu/Diagnostics/Internal events
Status for inputs and outputs: Main menu/Test/Function status, browse to the function
group of interest.
Remote communication related signals: Main menu/Test/Function status/
Communication/Remote communication
Test the correct functionality by simulating different kind of faults. Also check that sent and
received data is correctly transmitted and read.
A test connection is shown in figure 58. A binary input signal (BI) at End1 is configured to be
transferred through the communication link to End2. At End2 the received signal is configured
to control a binary output (BO). Check at End2 that the BI signal is received and the BO
operates.
Repeat the test for all the signals configured to be transmitted over the communication link.
IEC07000188 V1 EN-US
Figure 58: Test of RTC with I/O
11.17

Basic IED functions

11.17.1

Parameter setting group handling SETGRPS

Prepare the IED for verification of settings as outlined in section
chapter.
11.17.1.1

Verifying the settings

1.
Check the configuration of binary inputs that control the selection of the active setting
group.
2.
Browse to the ActiveGroup menu to achieve information about the active setting group.
The ActiveGroup menu is located on the local HMI underMain menu/Test/Function
status/Setting groups/ActiveGroup
Transformer protection RET670
Commissioning manual
© Copyright 2017 ABB. All rights reserved
Testing functionality by secondary injection
"Preparing for test"
in this
Section 11
SEMOD52026-1 v1
M11369-2 v4
M11369-4 v5
251