ABB Relion 670 Series Commissioning Manual page 133

Transformer protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 504 165-UEN E
X1Zx
IEC05000368 V4 EN-US
Figure 37: Distance protection characteristic with test points for phase-to-phase
Table 32:
Test point
1
2
3
4
5
6
7
8
9
10
11
Table continues on next page
Transformer protection RET670
Commissioning manual
X
2
1
11
10
12
120°
a
9
8
40% of RLdFw
80% of RLdFw
0.5 x RFPPZx
measurements
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Reach
Set value
X
X1
set
R
0
X
X1
set
R
R1
set
X
0.8 x X1
set
R
0.8 x R1
+ RFPPZx/2
set
X
0.5 x X1
set
R
0.5 x R1
+ RFPPZx/2
set
X
0.85 x RFPPZx x tan (ArgLd)
R
0.85 x RFPPZx
X
RLdFw x tan (ArgLd)
R
RLdFw
X
RLdFw x tan (ArgLd)
R
0
X
–0.2143 x RFPPZx/2
R
0.8 x RFPPZx/2
X
–0.4 x RLdFw x tan(ArgDir=20°)
R
0.4 x RLdFw
X
0.5 x X1
set
R
–0.23 x X1
set
X
0.8 x X1
set
R
–0.37 x X1
set
© Copyright 2017 ABB. All rights reserved
80%
3
50%
4
5
6
R (Ohm/phase)
7
13
c
20°
IEC05000368-4-en.vsdx
Comments
ArgLd = angle for the maximal load transfer
Exact: 0.8 x RFPPZx/2 (ArgDir=20°)
Exact –0.5 x R1
Exact –0.5 x R1
Testing functionality by secondary injection
x tan(ArgNegRes=30°)
set
x tan(ArgNegRes=30°)
set
Section 11
127