ABB Relion 670 Series Commissioning Manual page 194

Transformer protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
The set operate value in secondary amperes is calculated according to the following
equations:
First part of the characteristic (Restrain voltage ≤ 25% of
StartCurr
IECEQUATION2432 V1 EN-US
Second part of the characteristic (25% of
100*
 
IECEQUATION2433 V1 EN-US
Third part of the characteristic (
StartCurr
IECEQUATION2434 V1 EN-US
Example (rated secondary current = 1A):
CT ratio
VT ratio
StartCurr
VDepFact
UHighLimit
IBase
A test for each section of the characteristic of the function VRPVOC may be performed;
that may be achieved by applying the following voltages:
First section of the characteristic:
If
0,25*
lower than
Second section of the characteristic only:
If
0,25*
Last section of the characteristic:
If
higher than
188
In the following equations, restrain voltage is the magnitude of the
minimum phase-to-phase voltage in secondary volts.
CT
sec
IBase
×
×
×
100
CTprim
UBase ), valid when setting parameter VDepMode = Slope :
StartCurr
CT
sec
VDepFact
×
×
 ×
1
IBase
100
CTprim
100
(
)
UH
i i ghLimit
25
VT
sec
×
×
UBase
100
VTprim
CT
sec
IBase
×
×
100
CTprim
VDepMode = Slope , the minimum measured phase-to-phase voltage is lower than
UBase ; if VDepMode = Step , the minimum measured phase-to-phase voltage is
UHighLimit /100* UBase :
UL1: Ampl = 10 / √3; Angle = 0°
UL2: Ampl = 10 / √3; Angle = 240°
UL3: Ampl = 100 / √3; Angle = 120°
VDepMode = Slope , the minimum measured phase-to-phase voltage is between
UBase and UHighLimit /100* UBase :
UL1: Ampl = 50 / √3; Angle = 0°
UL2: Ampl = 50 / √3; Angle = 240°
UL3: Ampl = 100 / √3; Angle = 120°
VDepMode = either Slope or Step , the minimum measured phase-to-phase voltage is
UHighLimit /100* UBase :
© Copyright 2017 ABB. All rights reserved
VDepFact
100
UBase ≤ Restrain voltage ≤ UHighLimit /
25
×
×
Re
strainVoltage
U U Base
100
UHighLimit /100* UBase ≤ Restrain voltage):
10 000/1A
10 kV/100 V
100%
25%
100%
10 000 A
10 kV
UBase ):
VT
sec
StartCurr
C C T
sec
×
+
×
×
IBase
VTprim
100
CTprim
 
Transformer protection RET670
Commissioning manual
1MRK 504 165-UEN E
(Equation 95)
VDepFact
×
100
(Equation 96)
(Equation 97)