Mechanical planning and installation
Control cabinet assembly for AC500-eCo
5.2 Control cabinet assembly for AC500-eCo
PLC enclosure
To protect PLCs against:
●
unauthorized access,
●
dusting and pollution,
●
moisture and wetness and
●
mechanical damage,
control cabinet IP54 for common dry factory floor environment is suitable.
Maintain spacing from:
●
enclosure walls
●
cable ducts
●
adjacent equipment
Allow a minimum of 20 mm clearance on all sides. This provides ventilation and galvanic
isolation.
It is recommended to mount the modules on an grounded mounting plate, or an grounded DIN
rail, independent of the mounting location.
32
When vertically mounted, always place an end-stop terminal block on the
bottom and on the top of the modules to properly secure the modules.
With high vibration applications and horizontal mounting, we also recommend
to place end-stop terminals at the right and left side of the device to properly
secure the modules.