Wiring
EMC-conforming assembly and construction > Equipotential bonding
For supplying
Use the mains socket which is located inside the control cabinet.
the PC
Ä Chapter 5.1 "Control cabinet assembly for AC500 (Standard)" on page 30

6.2.5 Reference potential

Provide a uniform reference potential in the entire installation and ground all electrical
appliances if possible.
Route your grounding conductors in a star configuration so that no ground loops can occur.

6.2.6 Equipotential bonding

The Installation of equipotential bondings are necessary if there are present or expected poten-
tial differences between parts of your application.
62
The impedance of equipotential bonding must be equal or lower than 10 %
of the shield impedance of the shielded signal cables between the same
points.
The conductor cross section of a equipotential bonding must be 16 mm² to
withstand the maximum possible compensating current.
Equipotential bondings and shielded signal cables should be laid close to
each other.
Equipotential bondings must be connected to PE with low impedance.