Mechanical planning and installation

Control cabinet assembly for AC500 (Standard)

5 Mechanical planning and installation
5.1 Control cabinet assembly for AC500 (Standard)
PLC enclosure
To protect PLCs against:
unauthorized access,
dusting and pollution,
moisture and wetness and
mechanical damage,
control cabinet IP54 for common dry factory floor environment is suitable.
Maintain spacing from:
enclosure walls
wireways
adjacent equipment
Allow a minimum of 20 mm clearance on all sides. This provides ventilation and galvanic
isolation.
It is recommended to mount the modules on an grounded mounting plate, or an grounded DIN
rail, independent of the mounting location.
30
NOTICE!
PLC damage due to wrong enclosures
Due to their construction (degree of protection IP 20 according to EN 60529)
and their connection technology, the devices are suitable only for operation in
enclosed control cabinets.
3ADR011074, 1, en_US