The index of the module is in the right corner of the label.
NOTICE!
Risk of damage to I/O modules!
Modules with index below F0 can be damaged when inserted or removed from
the terminal unit in a powered system.
NOTICE!
Risk of damage to I/O modules!
Do not perform hot swapping if any I/O module with firmware version lower than
3.0.14 is part of the I/O configuration.
For min. required device index see table below.
3ADR011074, 1, en_US
Replace an I/O module with hot swap > Preconditions for using hot swap
Min. required device index for I/O module as of
FW Version 3.0.14
F0
D2
D4
D2
B2
B2
B3
D2
B2
D2
D2
B2
D1
D2
F0
D2
D2
D2
A2
D2
B2
B2
B2
A1
Maintenance