Other Faults - enphase IQ7 Installation And Operation Manual

Microinverters
Table of Contents

Advertisement

There are two ways to send a clear message to the microinverter. Note that the condition will not clear
after the sensor reset if the cause of the failure is still present. If the condition persists, contact your
installer.
Method 1: Clear this error using the Enphase Installer App
Log in to the Enphase Installer App and access the system.
Click the Events tab. The next screen shows a current "DC Resistance Low - Power Off"
condition for the system.
Click DC Resistance Low - Power Off.
Where "n" is the number of affected devices, click n devices (show details).
Click the serial number of the affected microinverter.
Click Reset DC Resistance Low - Power Off Sensor.
The system displays, "A DC Resistance Low- Power Off reset task was issued on [date and
time] for this microinverter and is still pending."
Method 2: Use the Enphase Installer App to clear the condition
On the list of detected microinverters, a green dot or red square appears to the left of each
microinverter serial number. A green dot indicates Status OK. A red square indicates an event
for that microinverter.
Tap the
to the left of the serial number to view details for a microinverter event.
If the microinverter status shows that there is an active DC Resistance Low – Power Off
condition, tap the
The app then indicates that a clear message was sent.

4.1.3 Other faults

All other faults are reported to the IQ Gateway. For troubleshooting procedures, refer to the IQ
Gateway Installation and Operation Manual at enphase.com/support.
25
IQ7/IQ7+/IQ7X/IQ7A Microinverters Installation and Operation Manual
to send the clear message to the affected microinverter.