Method 1: Clear this Error Using Enlighten
Log in to Enlighten and access the system.
Click the Events tab. The next screen shows a current "DC Resistance Low - Power Off"
condition for the system.
Click DC Resistance Low - Power Off.
Where "n" is the number of affected devices, click n devices (show details).
Click the serial number of the affected microinverter.
Click Reset DC Resistance Low - Power Off Sensor.
The system displays, "A DC Resistance Low- Power Off reset task was issued on [date and time]
for this microinverter and is still pending."
Method 2: Use Installer Toolkit to Clear the Condition
On the list of detected microinverters, a green dot or red square appears to the left of each microinverter
serial number. A green dot indicates Status OK. A red square indicates an event for that microinverter.
Tap the
to the left of the serial number to view details for a microinverter event.
If the microinverter status shows that there is an active DC Resistance Low – Power Off
condition, tap the
The app then indicates that a clear message was sent.

Other Faults

All other faults are reported to the Envoy. Refer to the Enphase IQ Envoy Installation and Operation
Manual at
enphase.com/support
23
to send the clear message to the affected microinverter.
for troubleshooting procedures.
© 2018 Enphase Energy Inc. All rights reserved.
IQ 7 / IQ 7+ / IQ 7X Micro Installation and Operation
141-00043-01