Pv Rapid Shutdown Equipment (Pvrse) - enphase IQ7 Installation And Operation Manual

Microinverters
Table of Contents

Advertisement

PV Rapid Shutdown Equipment (PVRSE)

This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and NEC-
2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems, for AC and DC
conductors, when installed according to the following requirements:
Microinverters and all DC connections must be installed inside the array boundary. Enphase
further requires installing the microinverters and DC connections under the PV module to
avoid direct exposure to rain, UV, and other harmful weather events.
The array boundary is defined as 305 mm (1 ft) from the array in all directions or 1 m (3 ft) from
the point of entry inside a building.
This rapid shutdown system must be provided with an initiating device and (or with) a status indicator,
which must be installed in a location accessible to first responders, or it must be connected to an
automatic system that initiates rapid shutdown upon the activation of a system disconnect or
activation of another type of emergency system.
The initiator shall be listed and identified as a disconnecting means that indicates whether it is in the
"off" or "on" position. Examples are:
Service disconnecting means
PV system disconnecting means
Readily accessible switch or circuit breaker
The handle position of a switch or circuit breaker is suitable for use as an indicator. Refer to NEC or
CSA C22.1-2015 for more information.
Additionally, in a prominent location near the initiator device, a placard or label must be provided with
a permanent marking including the following wording:
'PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN' The term 'PHOTOVOLTAIC' may be
replaced with 'PV.' The placard, label, or directory shall be reflective, with all letters capitalized and
having a minimum height of 9.5 mm (3/8") in white on a red background.
9
IQ7/IQ7+/IQ7X/IQ7A Microinverters Installation and Operation Manual
© 2023 Enphase Energy Inc. All rights reserved.
September 2023
IOM-00028-1.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Iq7+Iq7xIq7a