Electrical Installation
Installation Manual
4.8 Control Wiring
4.8.1 Control Cable Routing
Tie down all control wires to the designated control cable routing as shown in Figure 4.5, Figure 4.6, and Figure 4.7.
Remember to connect the shields in a proper way to ensure optimum electrical immunity.
4
4
Serial communication bus connection
Connections are made to the relevant options on the control card. For details, see the relevant serial communication bus
instructions. The cable must be placed in the provided path inside the adjustable frequency drive and tied down together
with other control wires (see Figure 4.5 and Figure 4.6).
Figure 4.5 Control Card Wiring Path for Frame Size D13
Figure 4.6 Control Card Wiring Path for Frame Size E9
MG21B322
Danfoss A/S © 10/2015 All rights reserved.
41