Specifications
Control card, RS-485 serial communication
Terminal number
Terminal number 61
The RS-485 serial communication circuit is functionally seated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Digital output
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Max. output current (sink or source)
Max. load at frequency output
Max. capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency outputs
1) Terminal 27 and 29 can also be programmed as input.
8
8
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output
Terminal number
Output voltage
Max. load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs
Relay 01 Terminal number
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Relay 02 Terminal number
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1) IEC 60947 parts 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300 V AC 2 A
92
®
VLT
AQUA Drive FC 202 Low Harmonic Drive
1)
on 1-3 (NC), 1-2 (NO) (resistive load)
(inductive load @ cosφ 0.4)
1)
1)
on 1-2 (NO), 1-3 (NC) (resistive load)
1)
(inductive load)
1)
on 4-5 (NO) (resistive load)
2)3)
on 4-5 (NO) (inductive load @ cosφ 0.4)
1)
1)
on 4-5 (NO) (resistive load)
1)
on 4-5 (NO) (inductive load)
1)
on 4-6 (NC) (resistive load)
on 4-6 (NC) (inductive load @ cosφ 0.4)
1)
1)
on 4-6 (NC) (resistive load)
1)
on 4-6 (NC) (inductive load)
Danfoss A/S © 10/2015 All rights reserved.
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Common for terminals 68 and 69
Max. error: 0.1% of full scale
24 V (+1, -3 V)
1-3 (break), 1-2 (make)
240 V AC, 0.2 A
24 V DC, 0.1 A
4-6 (break), 4-5 (make)
240 V AC, 0.2 A
24 V DC, 0.1 A
240 V AC, 0.2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24 V AC 20 mA
Overvoltage category III/pollution degree 2
2
1)
27, 29
0–24 V
40 mA
1 kΩ
10 nF
0 Hz
32 kHz
12 bit
13
200 mA
2
240 V AC, 2A
60 V DC, 1 A
400 V AC, 2 A
80 V DC, 2 A
240 V AC, 2 A
50 V DC, 2 A
MG21B322