6.3

Alarms

Introduction
The ET 200SP distributed I/O system generates the following alarms:
• Diagnostic alarms
• Maintenance alarms
6.3.1

Diagnostics alarms

Actions after a diagnostics alarm
There can be more than one diagnostics alarm at the same time. Each diagnostics alarm
initiates the following actions:
• The ERROR LED of the interface module flashes red.
• Diagnostics are reported as diagnostic error interrupts to the CPU of the IO controller and
can be read via data records.
• Incoming diagnostics alarms are saved to the diagnostics buffer of the I/O controller.
Table 6- 6
Diagnostics alarms, their meaning and possible remedies
Diagnostics alarm
Channel
Error
Type
(CET)
Configuration error:
0x0602
Module parameter
'potential group'
incorrect or wrong
Ba-
seUnit/TerminalBlock
on real configuration
slot <slot>
Configuration error:
0x0602
Station stop - missing
or wrong server
module
Configuration error:
0x0602
Permitted size of
backplane exceeded
Configuration error:
0x0602
Incorrect backplane
bus configuration in
slot <slot>
IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0)
Equipment Manual, 11/2023, A5E53132379-AA
Extended
Associated
Channel
value
Error
AddValue
Type
(ECET)
0x0691
Slot
0x0693
-
0x0698
-
0x0699
Slot
Interrupts, diagnostics, error, and system messages
Meaning / Cause
The configured BaseUnit or
the terminal block does not
match the real configuration.
No server module was
plugged in during startup of
an ET 200SP station.
The total width of the in-
stalled modules exceeds the
permitted configuration
length of 1 000 mm.
The maximum power re-
quirement of all installed
modules exceeds 2 100 mA
in total.
The associated value <slot>
indicates the faulty slot.
6.3 Alarms
Remedy
Check for suitable base unit or
terminal block.
Check that the server module
is installed correctly in the
rack.
Check that the configuration
of the backplane bus does not
exceed the permitted size.
Check backplane mounting.
41