Menu 0 (sub block)

Menu 0 can be accessed by 2 methods:
1. Pr 11.44 (SE14, 0.35) = 0. Sub block mode.
2. Pr 11.44 (SE14, 0.35) <>0. Linear mode.
Menu 23 contains the parameters to allow menu 0 to be customized in
sub block mode. The first sub block is a user defined area (USEr) which
is configured by the parameters in menu 22. As default there are no
parameters configured to the user sub block and so it is empty. The next
7 sub blocks are pre-defined. Access to the pre-defined blocks is
enabled or disabled by Pr 23.03 to Pr 23.09.
Movement between sub blocks is achieved with the left and right keys.
Pr 23.01 contains all the sub block headers.
Table 5-1 and Figure 5-5 show the result of the direction keys when
Pr 11.44 (SE14, 0.35) is set to L1 (0). When Pr 11.44 (SE14, 0.35)is not
0 the left and right keys will allow access to the advance parameter set
and menu 0 will become a linear menu.

Table 5-1 Keypad navigation

Starting location
Action
Right
Left
Header
Up
Down
Right
Left
Parameter
Up
Down
When moving to the user block header, the user block header is only
displayed if there are some valid parameters in the block. When moving
between pre-defined header blocks the pre-defined header block is only
displayed if the pre-defined block is enabled.
When moving between parameters within a block, only valid parameters
are displayed.
Figure 5-5 Sub block navigation
SEt UP
diAGnoS
Headers
Quantum MP User Guide
Issue: A3
Electrical
Getting
Basic
Installation
Started
parameters
Finishing location
Next header
Previous header
First parameter in header block
Last parameter in header block
Next header
Previous header
Next parameter in header block
Previous parameter in header block
SE00
SE13
di01
di14
triPS
inPut
in01
in10
www.emersonct.com
Running the
SMARTCARD
Optimization
Motor
Operation
Coding
The coding defines the attributes of the parameter as follows.
Coding
{X.XX}
Copied Menu 0 or advanced parameter
Bit
1 bit parameter: 'On' or 'OFF' on the display
Bi
Bipolar parameter
Uni
Unipolar parameter
Txt
Text: the parameter uses text strings instead of numbers.
SP
Spare: not used
Filtered: some parameters which can have rapidly changing
FI
values are filtered when displayed on the drive keypad for
easy viewing.
Destination pointer parameter: This parameter can be used
DE
to set up the location (i.e. menu/parameter number) where
the destination data is to be routed.
Variable maximum: the maximum of this parameter can
VM
vary.
Decimal place: indicates the number of decimal places
DP
used by this parameter.
No default: when defaults are loaded (except when the
ND
drive is manufactured or on EEPROM failure) this
parameter is not modified.
Rating dependent: this parameter is likely to have different
values and ranges with drives of different voltage and
current ratings. Parameters with this attribute will not be
transferred to the destination drive by SMARTCARDs when
RA
the rating of the destination drive is different from the
source drive and the file is a parameter file. However, the
value will be transferred if only the current rating is different
and the file is a differences from default type file.
Not copied: not transferred to or from SMARTCARDs
NC
during copying.
NV
Not visible: not visible on the keypad.
PT
Protected: cannot be used as a destination.
User save: parameter saved in drive EEPROM when the
US
user initiates a parameter save.
RW
Read/write: can be written by the user.
RO
Read only: can only be read by the user.
Bit default one/unsigned: Bit parameters with this flag set to
one have a default of one (all other bit parameters have a
BU
default of zero. Non-bit parameters are unipolar if this flag is
one.
Power-down save: parameter automatically saved in drive
EEPROM when the under volts (UV) trip occurs. Power-
PS
down save parameters are also saved in the drive when the
user initiates a parameter save.
23.01
Sub block headers
RO
Txt
NC
USEr (0), SEt UP (1),
diAGnoS (2), triPS (3), SP
LOOP (4), Fb SP (5), SintEr
(6), inPut (7)
Defines the sub block headers. Can be used by the SM-Keypad Plus to
display the same strings as the SM-Keypad.
Onboard
Advanced
Technical
Diagnostics
PLC
Parameters
Data
Attribute
USEr (0)
UL
Information
PT
BU