Table 3-5 Dynamic Braking Resistor (DB+ and DB-) terminals
Model Connection type
All
Slotted lug
3.9

Electrical terminals - Size 2

3.9.1
Location of the power and ground terminals
Figure 3-12 Location of the power and ground terminals
3.9.2
Terminal sizes and torque settings
To avoid a fire hazard and maintain validity of the UL listing,
adhere to the specified tightening torques for the power and
ground terminals. Refer to the following tables.
WARNING
24
Electrical
Getting
Basic
Installation
Started
parameters
Torque setting
Wire gauge
Nm
14-10 AWG
4
8 AWG
4.5
6-4 AWG
5
2 AWG
5.6
L1
FIG 4A
L1
DANGER
HIGH VOLTAGE
DANGER
HIGH VOLTAGE
A+
A2
Running the
SMARTCARD
Optimization
Motor
Operation

Table 3-6 Suppression Resistor (SR+ and SR-) terminals

Model Connection type
lb ft
2.92
3.33
All
Slotted lug
3.75
4.17
L2
L3
L2
L3
GND
A-
GND
A1
3.9.3
Torque settings
Table 3-7 Drive control, status relay and encoder terminal data
Model
All
www.emersonct.com
Onboard
Advanced
Technical
PLC
Parameters
Data
Wire gauge
14-10 AWG
8 AWG
6-4 AWG
2 AWG
GND
GND
120Vac Logic
Terminals
Connection type
Plug-in terminal block
Quantum MP User Guide
UL
Diagnostics
Information
Torque setting
Nm
lb in
4
2.92
4.5
3.33
5
3.75
5.6
4.17
Torque setting
0.5 Nm 0.4 lb ft