Specifications - YASKAWA JOHB-SMP3-MA Technical Manual

Modbus tcp/ip
Table of Contents

Advertisement

3.
Ground the largest possible surface area of the shield to the metal panel.
Yaskawa recommends using cable clamps.
A - Braided shield cable
B - Metal panel
11

Specifications

Specifications
Items
Model
Supported Messages
Modbus TCP/IP Specifications
Recommended Connector Type
Physical Layer Type
YASKAWA SIEP C730600 0IB Modbus TCP/IP Technical Manual
Figure 10.3 Option Installation for CE Compliance: GA500, HV600
Figure 10.4 Option Installation for CE Compliance: FP605
Figure 10.5 Ground Area
Table 11.1 Option Specifications
JOHB-SMP3
• Read Multiple Registers (03 (Hex.))
• Write Single Register (06 (Hex.))
• Write Multiple Registers (10 (Hex.))
• Read and Write Registers (17 (Hex.))
Commands that support multiple registers have a maximum Read and Write size of 16 registers.
Modbus-IDA
Shielded Cat5e cable
Ethernet Isolated Physical Layer
C - Cable clamp (conductive)
Specifications
11 Specifications
43