F7-10
Gateway Address 2
(03EE)
F7-11
Gateway Address 3
(03EF)
F7-12
Gateway Address 4
(03F0)
F7-13
Address Startup Mode
(03F1)
F7-14
Duplex Mode Selection
(03F2)
F7-15
Communication Speed
Selection
(03F3)
F7-16
Timeout Value
(03F4)
H5-11
Communications ENTER
Function Selection
(043C)
(Function common to
communication option)
YASKAWA SIEP C730600 0IB Modbus TCP/IP Technical Manual
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Gateway address. Sets the second most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Gateway address. Sets the third most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Gateway address. Parameter F7-12 sets the fourth most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Selects how the option address is set.
0 : Static (Use F7-01 to F7-12 to set.)
1 : BOOTP (Use network address.)
2 : DHCP (Use network address.)
Note:
You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets duplex mode settings (Port 1 (CN1A)/Port 2 (CN1B)).
0 : Half/Half (Half Duplex/Half Duplex)
1 : Auto/Auto (Auto Negotiation/Auto Negotiation)
2 : Full/Full (Full Duplex/Full Duplex)
3 : Half/Auto (Half Duplex/Auto Negotiation)
4 : Half/Full (Half Duplex/Full Duplex)
5 : Auto/Half (Auto Negotiation/Half Duplex)
6 : Auto/Full (Auto Negotiation/Full Duplex)
7 : Full/Half (Full Duplex/Half Duplex)
8 : Full/Auto (Full Duplex/Auto Negotiation)
Note:
You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the communications speed (Port 1 (CN1A)/Port 2 (CN1B)).
10 : 10/10 Mbps (10 Mbps/10 Mbps)
100 : 100/100 Mbps (100 Mbps/100 Mbps)
101 : [Not Used/No function] 10/100 Mbps (10 Mbps/100 Mbps)
102 : [Not Used/No function] 100/10 Mbps (100 Mbps/10 Mbps)
Note:
• F7-15 is only effective when the port is set to half or full duplex in F7-14 [Duplex Mode
Selection].
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the detection time for a communications timeout.
Note:
• Set this parameter to 0.0 to disable the connection timeout function.
• This parameter is not available in all 1000-series drives.
• Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
Sets when an Enter command is necessary to use MEMOBUS/Modbus communications to change
parameter values.
0 : Parameter changes are activated when ENTER command is written
1 : Parameter changes are activated immediately. No ENTER command is necessary.
Description
6 Related Drive Parameters
Default
(Range)
168
(0 - 255)
1
(0 - 255)
1
(0 - 255)
2
(0 - 2)
1
(0 - 8)
10
(10 - 102)
0.0 s
(0.0 s - 30.0 s)
0
(0, 1)
23