6 Related Drive Parameters
No.
Name
(Hex.)
F6-14
Bus Error Auto Reset
(03BB)
F6-15
Comm. Option Parameters
Reload
(0B5B)
F7-01
IP Address 1
(03E5)
F7-02
IP Address 2
(03E6)
F7-03
IP Address 3
(03E7)
F7-04
IP Address 4
(03E8)
F7-05
Subnet Mask 1
(03E9)
F7-06
Subnet Mask 2
(03EA)
F7-07
Subnet Mask 3
(03EB)
F7-08
Subnet Mask 4
(03EC)
F7-09
Gateway Address 1
(03ED)
22
Note:
When you set F6-08 to 1 and you then use A1-03 to initialize the drive, the drive will not
change this setting value.
Enables and disables the automatic reset of a bUS [Option Communication Error] fault.
0 : Disabled
1 : Enabled
Note:
• This parameter is not available in all 1000-series drives.
• Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
Sets when the drive will activate the F6-xx/F7-xx communications-related parameters that you
changed. Use this parameter as an alternative to cycling power to the drive to active parameters.
0 : Reload at Next Power Cycle
1 : Reload Now
2 : Cancel Reload Request
Note:
• F6-15 is reset to 0 after setting 1 or 2.
• This parameter is not available in all 1000-series drives.
• Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
Sets the static/fixed IP address. Sets the most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed IP address. Sets the second most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed IP address. Sets the third most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed IP address. Sets the fourth most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Subnet Mask. Sets the most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Subnet Mask. Sets the second most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Subnet Mask. Sets the third most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Subnet Mask. Parameter F7-08 sets the fourth most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Gateway address. Sets the most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
Description
YASKAWA SIEP C730600 0IB Modbus TCP/IP Technical Manual
Default
(Range)
0
(0, 1)
0
(0 - 2)
192
(0 - 255)
168
(0 - 255)
1
(0 - 255)
20
(0 - 255)
255
(0 - 255)
255
(0 - 255)
255
(0 - 255)
0
(0 - 255)
192
(0 - 255)