Huawei UPS5000-E-200K-FM Quick Manual
Huawei UPS5000-E-200K-FM Quick Manual

Huawei UPS5000-E-200K-FM Quick Manual

Hide thumbs Also See for UPS5000-E-200K-FM:

Advertisement

UPS5000-E-(50 kVA-200 kVA)
Quick Guide (50 kVA Power Modules)
Issue: 11
Part Number: 31507655
Date: 2022-12-30
1
Overview
UPS Model
Cabling Mode
UPS5000-E-
Routed in and out from the
200K-SM
top or bottom
Routed in and out from the
UPS5000-E-
top, routed in and out from
200K-FM
the bottom (install a cable
entry cabinet)
The UPS5000-E-200K-SM is a standard configuration model. The UPS5000-E-200K-FM is a full
configuration model. A UPS in standard configuration has no mains input switch, bypass input
switch, or output switch.
1. Before installation, read the user manual carefully to get familiar with product information
and safety precautions.
2. Use insulated tools when installing the equipment.
3. Only engineers certified by Huawei or its agent are allowed to install, commission, and
maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the
resulting UPS faults are beyond the warranty scope of Huawei.
4. This document describes the installation procedure for a single UPS. For details about how to
install a parallel system, contact Huawei technical support.
Weight (Full
Capacity
Configuration)
330 kg
50 kVA,
100 kVA,
150 kVA,
390 kg
200 kVA
Copyright © Huawei Digital Power Technologies Co., Ltd. 2022.
1
All rights reserved.
Dimensions (H x W
x D)
2000 mm x 600 mm
x 850 mm

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UPS5000-E-200K-FM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Huawei UPS5000-E-200K-FM

  • Page 1 2. Use insulated tools when installing the equipment. 3. Only engineers certified by Huawei or its agent are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the resulting UPS faults are beyond the warranty scope of Huawei.
  • Page 2: Installing The Ups

    UPS5000-E-200K-SM UPS5000-E-200K-FM (1) Power modules (2) Bypass module (3) Control module (CM) (4) Power distribution subrack cover (5) Filler panel (6) Monitor display unit (MDU) (7) Maintenance bypass switch (8) Folder (9) Bypass input switch (10) Main input switch (11) Output switch...
  • Page 3: Connecting Cables

    2. Use a hammer drill to drill four holes for installing expansion bolts and then install four expansion bolts in the holes. Remove the bolt, spring washer, and flat washer. 3. Slide the cabinet on its castors to the installation position. 4.
  • Page 4: Ups Cable Connection Reference

    UPS Cable Connection Reference • Prepare cables away from the cabinets to prevent scraps from falling inside. Cable scraps may ignite and cause personal injury or device damage. • After cables have been installed, clean the cabinets in a timely manner. Keep the cabinets and surrounding environment clean and tidy.
  • Page 5 Connecting Cables Connecting Cables to the UPS5000-E-200K-SM 2. Remove the cover from the power Scenario 1: Routing Cables from the Top distribution subrack. 1. Remove the small covers of the cabinet top. The cover can be opened only if the maintenance bypass switch is OFF.
  • Page 6 5. Connect mains and bypass input power 6. Connect output power cables. cables. 7. Connect battery cables. Route a neutral wire from the middle of the positive and negative battery strings. Take a battery string consisting of 40 batteries as an example. A neutral wire is routed from the middle of positive and negative battery strings, each consisting of 20 batteries.
  • Page 7 8. Connect the signal cable. Scenario 2: Routing Cables from the Bottom 1. Remove the cover from the power distribution subrack. The number and 2. Remove the copper bars between mains color of signal cables input terminals and bypass input terminals. in the figure are for 3.
  • Page 8 Connecting Cables to the UPS5000-E-200K-FM Scenario 1: Routing Cables from the Top 1. Remove a certain number of small covers 2. Remove the cover from the power from the top of the cabinet based on site distribution subrack. conditions. 3. Remove the copper bars between mains 4.
  • Page 9 5. Connect mains input power cables. 6. Connect bypass input power cables. Route a neutral wire from the middle of the 7. Connect battery cables. positive and negative battery strings. Take a battery string consisting of 40 batteries as an example. A neutral wire is routed from the middle of positive and negative battery strings, each consisting of 20 batteries.
  • Page 10 8. Connect output power cables. 9. Connect the signal cable. Scenario 2: Routing Cables from the Bottom A cable entry cabinet needs to be installed when cables are routed from the bottom. This document uses the cable entry cabinet installed on the right of the UPS cabinet as an example. 1.
  • Page 11 5. Place the cable entry cabinet on the right of 7. (Optional) Secure the cable entry cabinet the UPS cabinet. to the ground. 6. Install the front and rear connecting kits. 8. Install an equipotential plate. 9. Remove a certain number of small covers 10.Remove the signal cable trough cover from from the bottom of the cable entry cabinet the cable entry cabinet.
  • Page 12: Verifying The Installation

    11.Connect the signal cable. 12.Connect power cables. • The figure shows the signal cable routing For the screw specifications and torque used and is for reference only. Connect the for connecting cables in a bottom cable cable based on the actual situation. routing scenario, refer to the top cable •...
  • Page 13: Powering On And Starting The Ups

    Close the upstream bypass and mains input switches. (Full configuration model) Close the UPS bypass input switch, output switch, and mains input witch. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar.
  • Page 14: Initial Startup

    Initial Startup 1. Obtain the startup password through the app. After the application is approved, enter the password on the service authorization screen of the device to complete device authorization. Technical support engineers can obtain the service authorization code through the app. For Data Center Facility Deployment Guide details, see the 2.
  • Page 15: Shutting Down The Ups

    System User LCD Preset Password WebUI Preset Password admin (system administrator) 000001 Changeme operator (common user) 000001 Changeme Powering On Loads 1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears from the MDU. 2.
  • Page 16 Huawei Digital Power Technologies Co., Ltd. Huawei Digital Power Antuoshan Headquarters Futian, Shenzhen 518043 People’s Republic of China www.huawei.com...