Mounting and sensor wiring

2.1 
Mounting and sensor wiring for integral-mount
transmitters
There are no separate mounting requirements for integral transmitters, and there is no
need to connect wiring between the transmitter and the sensor.
2.2 
Mount the transmitter to a wall or instrument
pole
There are two options available for mounting the transmitter:
Mount the transmitter to a wall or flat surface.
Mount the transmitter to an instrument pole.
Prerequisites
If you are mounting the transmitter to a wall or flat surface:
If you are mounting the transmitter to an instrument pole:
Procedure
1. Attach the mounting bracket to the transmitter and tighten the screws.
Installation Manual
Ensure that the surface is flat and rigid and that it does not vibrate or move
excessively.
Confirm that you have the necessary tools and the mounting kit shipped with the
transmitter.
Confirm that the mounting surface, method, and surface structure ensures
sufficient strength to secure the transmitter (e.g. when mounting to drywall use
a toggle type drywall anchor).
Ensure that the instrument pole extends at least 12 in (305 mm) from a rigid base,
and is no more than 2.5 in (64 mm) in diameter.
Confirm that you have the necessary tools, and the instrument-pole mounting kit
shipped with the transmitter.
Mounting and sensor wiring
October 2023
11