CHAPTER 6: INSTALL – VENT & COMBUSTION AIR PIPING

6.5.4 Air Intake and Vent Starter Pieces

Venting must be supported per guidelines listed in the National Mechanical Code, Section 305,
Table 305.4 or as local codes dictate.
Figure 6-2 shows how the air intake and vent outlet adapters are assembled. To connect a vent
pipe to the air intake and vent outlets, proceed as follows while referring to Figures 6-2 and 6-3:
Installing the Air Intake and Vent Connections
1.
Apply a suitable sealant (Viton RTV or equivalent) to the inside diameter of both the air inlet
adapter and vent outlet adaptor (see Figure 6-2) to create an airtight seal with the piping.
Install air inlet piping and exhaust vent piping 3" deep into the adapters.
2.
3.
Tighten each adaptor hose clamp (Fig. 6-2) to secure each adaptor to its respective piping.
Drill a 1/4" hole into the exhaust outlet piping in approximately the position as shown in
4.
Figure 6-2. This port will be used as a combustion analysis port during the combustion
calibration procedure described in Section 8.2. Procure a suitable cap to plug this port when
it is not being used for calibration.
WARNING!
You must ensure that a suitable cap is used to seal the calibration analysis port during
normal operation to prevent the escape of dangerous exhaust gases.
STEP 2:
AIR INLET
PIPING (FIELD
PROVIDED)
STEP 1:
VITON RTV
ADHESIVE
BOLTS
AIR INLET
ADAPTOR
ADAPTOR
GASKET
AIR
INLET
Figure 6-2: Air Intake and Vent Connection Installation
OMM-0100_E • GF-146 • 11/15/2019
STEP 3:
HOSE
CLAMP
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
STEP 4: CAP (FIELD PROVIDED)
COMBUSTION ANALYSIS
PORT (FIELD INSTALLED)
STEP 2: EXHAUST
OUTLET PIPING
(FIELD PROVIDED)
BOLTS
EXHAUST OUTLET
ADAPTOR
ADAPTOR GASKET
EXHAUST SEAL
GASKET
EXHAUST CHIMNEY
EXHAUST SEAL
GASKET FITS INTO
INNER GROOVE OF FLUE
EXHAUST CHIMNEY