Watts Aerco TAG-0072 GF-146-E Operation & Maintenance Manual page 140

Natural gas and propane gas modulating condensing boilers and water heaters
Table of Contents

Advertisement

AM Series Boilers and Water Heaters User Manual
CHAPTER 10 – MAINTENANCE
Condensate System Inspection and Maintenance - Continued
8.
Replace the condensate cover and reinsert the condensate collection tank assembly back
into the unit.
WARNING!
The condensate collection tank must be filled with water to prevent flue gas emissions from
escaping during unit operation. Failure to comply with this requirement can result in
dangerous levels of carbon monoxide.
9.
Open the manual gas shutoff valve.
10.
Restore electrical power to the unit and return to service.
WARNING!
The condensate neutralizer tank MUST be installed correctly into the unit, as shown in Figure
4-8. If you do not install the condensate collection tank into its correct position, it will result in
combustion gases will entering the room and creating a dangerous condition.
OMM-0100_E • GF-146 • 11/15/2019