CHAPTER 8 – UNIT START-UP

8.10 Heating System Pressure Test

If the pressure inside the heating circuit falls below the minimum pressure for the system, the
appliance switches off and the display shows Err 59 to indicate that it is necessary to restore the
correct pressure. Open the filling valve and check the pressure on the pressure gauge "M" of
Figure 8-1. Err 59 will disappear when the pressure is back at the right value. To prevent
accidental relief valve openings, fill the heating circuit slowly.
This value is adjustable via parameter 3022.
CAUTION!
Continual fresh make-up water will reduce boiler life. Mineral buildup in the heat exchanger
reduces heat transfer, overheats the stainless steel heat exchanger, and causes failure.
Addition of oxygen carried in by makeup water can cause internal corrosion in system
components. Leaks in boiler or piping must be repaired at once to prevent makeup water
entering the boiler.
OMM-0100_E • GF-146 • 11/15/2019
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Page 102 of 170