Min/Max Allowable Combustion Air And Vent Piping Lengths; General Venting And Combustion Air Piping Installation; Specific Vent Installations - Watts Aerco TAG-0072 GF-146-E Operation & Maintenance Manual

Natural gas and propane gas modulating condensing boilers and water heaters
Table of Contents

Advertisement

AM Series Boiler & Water Heater User Manual
CHAPTER 6: INSTALL – VENT & COMBUSTION AIR PIPING

6.3 Min/Max Allowable Combustion Air and Vent Piping Lengths

The maximum length of the two pipes vent system is 120 equivalent feet (air intake plus
flue exhaust). However, each single pipe can't be longer than 60 feet.
Each 45° elbow inserted in the venting system has a loss of pressure equivalent to 3 feet of
linear pipe.
Each 90° elbow inserted in the venting system has a loss of pressure equivalent to 6 feet of
linear pipe.
The minimum length of the venting system is 1 foot (357 mm).

6.4 General Venting and Combustion Air Piping Installation

The unit must be vented and supplied with combustion and ventilation air as described in this
section. Ensure the vent and air piping and the combustion air supply comply with these
instructions regarding vent system, air system, and combustion air quality. Inspect finished vent
and air piping thoroughly to ensure all are airtight and comply with the instructions provided and
with all requirements of all applicable codes.
WARNING!
Failure to provide a properly installed vent and air system will cause severe personal injury or
death.
Using vent materials other than those listed in Table 6-1, failure to properly seal all seams
and joints, mixing of venting materials, or failure to follow vent pipe and fittings
manufacturer's instructions can result in injury, death or property damage.
Table 6-1: Approved Venting Materials

6.5 Specific Vent Installations

Choose acceptable combustion air inlet pipe materials from the following list:
PVC, CPVC or ABS
Polypropylene material to be sealed to specification of its manufacturer.
AL29-4C, stainless steel material to be sealed to specification of its manufacturer. If
using stainless steel, refer to section 6.5.1.
OMM-0100_E • GF-146 • 11/15/2019
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Page 68 of 170

Advertisement

Table of Contents
loading