10.19 Ignition and Flame Detection Sensor Electrode Positioning

For the heater to work properly the electrodes must be positioned as listed below and shown in
Figure 10-7:
Ignition and Flame Detection Electrode Positioning
2.
To insure correct functioning of the burner, the distances listed below should be carefully
verified by hand using calipers.
The distance between the ignition electrodes "A" and "B", must be between 0.08 in (2
mm), and 0.10 in (2.5 mm);
The distance of the ignition electrodes to the burner surface must be between 0.20 in
(5.0 mm), and 0.22 in (5.5 mm);
The distance of the flame detection electrode to the burner surface must be between
0.23 in (6.0 mm), and 0.27 in (7.0 mm).
Figure 10-7: Positioning the Ignition & Flame Detection Sensor Electrodes
OMM-0100_E • GF-146 • 11/15/2019