CHAPTER 3: INSTALLATION – SITE

3.10.1 Transporting a Standard AM Unit

Transport a standard AM boiler or water heater to its installation location as follows.
Transporting a
Remove the lower cover "A" at front of the AM unit by pulling it off.
1.
Remove the screw & washer "B" (Figure 3-4), which fastens the pallet to the unit front.
2.
Figure 3-4: Removing the Unit Front from Wood Pallet
Remove the screw and washer "C" (Figure 3-5), which fastens the pallet to the unit rear.
3.
Figure 3-5: Removing the Unit rear from Wood Pallet
Install the two factory supplied eyebolts "D" on the upper side of the unit and attach chains
4.
or straps to lifting ring/hook "E" as shown in Figure 3-6.
Figure 3-6: Removing the Unit from Wood Pallet (Lifting)
OMM-0100_E • GF-146 • 11/15/2019