SECTION 2 – INSTALLATION

2.13 COMBUSTION AIR

The Benchmark Venting and Combustion Air Design Guide, TAG-0022 (GF-2050) MUST be
consulted before any inlet air venting is designed or installed. Air supply is a direct requirement
of ANSI 223.1, NFPA-54, CSA B149.1 and local codes. These codes should be consulted
before a permanent design is determined.
The combustion air must be free of chlorine, halogenated hydrocarbons, other chemicals that
can become hazardous when used in gas-fired equipment and other combustion products.
Common sources of these compounds are swimming pools, degreasing compounds, plastic
processing, and refrigerants. Whenever the environment contains these types of chemicals,
combustion air MUST be supplied from a clean area outdoors for the protection and longevity of
the equipment and warranty validation.
If combustion air is supplied directly to the unit(s) though air duct(s), see section 2.13.1 below.
If combustion air is not supplied through air ducts, it must be supplied to the unit(s) through two
permanent openings. These two openings must have a free area of not less than one square
2
inch (6.5 cm
) for each 4000 BTUs (1.17 kW) input for each unit. The free area must take
into account restrictions such as louvers and bird screens.
For Canada installations, refer to the requirements specified in CSA B149.1-10, sections 8.4.1
and 8.4.3.

2.13.1 DUCTED COMBUSTION AIR

For ducted combustion air installations, the air ductwork must be attached directly to the air inlet
connection on the sheet metal enclosure. Consult the Benchmark Venting and Combustion Air
Design Guide, TAG-0022 (GF-2050) when designing combustion air ducting.
In a ducted combustion air application, the combustion air ducting pressure losses must be
taken into account when calculating the total maximum allowable venting run. When using the
unit in a ducted combustion air configuration, the minimum diameter connection at the unit is:
TABLE 2-4: Air Duct Minimum Diameter
Benchmark Model
BMK750 – BMK1500
BMK2000 – BMK3000
BMK4000 and 5000N
BMK5000 & BMK6000

2.14 BST SEQUENCING ISOLATION VALVE INSTALLATION

All Benchmark units are pre-wired with a connection for an optional motorized external
sequencing isolation valve (P/N 92084-TAB). This valve is an integral component of AERCO's
on-board Boiler Sequencing Technology (BST) solution. BST allows sites with multiple boilers to
have one boiler, designated the "Manager," manage the other boilers at the site, designated as
"Clients" in such a way that the efficiency of the entire boiler array is maximized.
GF-210 •
OMM-136_H
Duct Diameter
6-inch (15.2 cm) diameter connection
8-inch (20.3 cm) diameter connection
10-inch (25.4 cm) diameter connection
14-inch (35.6 cm) diameter connection
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST